3-phase 400Hz 115VAC inverters 1800VA with input voltages of 12V, 24V, 48V DC

3-phase 400Hz inverter
400Hz tutorial
400Hz Tutorial
  • Crystal controlled for precise timing for digital clocks and controllers
  • Suitable for any system that requires less than 1800 watts continuous.
  • Ultra quiet with no electrical interference.
  • Very rugged and reliable.
  • Low voltage warning and shutdown to protect the batteries
  • Extra heavy filtering to isolate noise from equipment sharing the same battery
  • Isolated, can be used in positive or negative ground applications.
1800VA 400Hz static inverter 12 volts DC to 115 VAC 400Hz 3-Phase 24 volts DC to 115VAC 400Hz 3-Phase 48 volts DC to 115VAC 400Hz 3-Phase
Part Number
and Price
PSEC1800-12-3P-400Hz
Allow up to 8-16 weeks for manufacturing
Call for Pricing
PSEC1800-24-3P-400Hz
Allow up to 8-16 weeks for manufacturing
PSEC1800-48-3P-400Hz
Allow up to 8-16 weeks for manufacturing
Country of Origin USA USA USA
Input Voltage 10-15VDC 20-30VDC 40-60VDC
Output Voltage 115V line to neutral
200V line to line
115V line to neutral
200V line to line
115V line to neutral
200V line to line
Output Frequency 400Hz pure sine wave
Output Power 1800 VA 1800 VA 1800 VA
Output current limit? Yes
Operating Temperature Range 0°C to +50°C
Humidity 5-95% non-condensing
Efficiency 78 % minimum at full load
Duty Cycle Continuous power 24 hours per day
Harmonic Distortion <5% at full load
Line Regulation < ±0.5%
Load regulation < ±6% over the range of 10% load to 100% load
Temperature Drift <0.05% per °C over operating temperature range
Isolation 1500VDC Input to output, Output to chassis 2250VDC
Remote power on/off No
Input Connections Compression Terminal
Input Protection Thermal fuse, Inrush current limiting, Reverse polarity protection
Output Protection Current limiting with short circuit protection, thermal shutdown with automatic recovery in case of continuous overload or insufficient airflow
EMI Meets EN55022 Class B
Agency compliance Built to meet C22.2 No. 107.1 - 01 and UL 458
Warranty* 2 years *Warranty depends on installation within good engineering practice.


[Home] [PowerStream] [Site Map]
[Tech Resources]
[Policy and Privacy] [Contact Us]

Thank you for considering PowerStream

PowerStream Technology
1163 South 1680 West
Orem, Utah 84058
USA

Phone: 801-764-9060
Fax: 801-764-9061

© Copyright 2000, 2002, 2003, 2004, 2005, 2006, 2008,2009, 2010, 2011, 2012, 2013, 2014, 2015, 2016, 2017, 2018, 2019, 2020, 2021, 2022
Lund Instrument Engineering, Inc. All rights reserved.

Google Author Verification