1200 watt
DC/AC inverters |
300 volts DC to 115 VAC 1200VA |
300 volts DC to 220VAC 1200VA |
300VDC to 115VAC 2400VA |
300VDC to 220VAC 2400VA |
Part Number and
Price |
IPSi1205-250-110 Allow up to 8-12 weeks for manufacturing
$2553 |
IPSi1205-250-220 Allow up to 8-12 weeks for
manufacturing $2639
|
IPSi2405-250-110 Allow up to 8-12 weeks for manufacturing
$3103 |
IPSi2405-250-220 Allow up to 8-12 weeks for manufacturing
$3189 |
Country of Origin |
Canada, NAFTA eligible |
Canada, NAFTA eligible |
Canada, NAFTA eligible |
Canada, NAFTA eligible |
Input Voltage |
200-400VDC |
200-400VDC |
200-400VDC |
200-400VDC |
Input Current |
< 20A |
< 20A |
< 40A |
< 40A |
Output Voltage |
110VAC ± 2 |
220VAC ±4 |
115VAC ± 2 |
220VAC ± 4 |
Output Frequency |
60 Hz or 50Hz pure sine wave User selectable frequency |
Continuous Ouput
Current |
11 Amps |
5.5 Amps |
22 Amps |
11 Amps |
Peak Output
Current |
22A 10 seconds 13A 60 seconds |
11A 10 seconds 6.5A 60 seconds |
44A 10 seconds 26A 60 seconds |
22A 10 seconds 13A 60 seconds |
Output Power |
1200 VA |
1200 VA |
2400 VA |
2400 VA |
Load Crest Factor |
3 |
3 |
3 |
3 |
Overvoltage protection |
> 400 VDC |
Undervoltage protection |
< 180 VDC |
Output current limit? |
Yes |
Operating Temperature
Range |
0°C to +50°C |
Humidity |
5-95% non-condensing |
Efficiency |
80 % minimum at full load |
Duty Cycle |
Continuous power 24 hours per day |
Harmonic Distortion |
<5% at full load |
Line Regulation |
< ±0.5% |
Load regulation |
< ±6% over the range of 10% load to 100% load |
Temperature Drift |
<0.05% per °C over operating temperature range |
Isolation |
1200VDC Input to output 2250VDC, Output to chassis 2250VDC |
Remote power on/off |
Optional |
Connections |
AC OUT 2x - Universal AC Receptable S.203013 AC Out
1x Phoenix VDFK4 terminal block
DC In Phoenix VFK-4 terminal block for
AWG 10-24 wire |
Wiring
recommenations |
Output AWG 10-20 Input AWG 10-16 |
Output AWG 10-22 Input AWG 10-16 |
Output AWG 10-16 Input AWG 10-12 |
Output AWG 10-20 Input AWG 10-12 |
Input Protction |
Thermal fuse, Inrush current limiting, Reverse polarity
protection |
Output Protection |
Current limiting with short circuit protection, thermal shutdown
with automatic recovery in case of continuous overload or insufficient
airflow |
EMI |
Meets EN55022 Class A |
Agency compliance |
Compliance to C22.2 No. 107.1 - 01 and UL 458 |
Dimensions |
5.6 x 11.75 x 18.68 inches 13.5 x 35.1 x 42.5 cm |
Weight |
24 Kg (52.5 lbs) |
Cooling |
Fan comes on when needed |
Warranty* |
5 years *Warranty depends on installation within good
engineering practice. |